Showing posts with label blackout. Show all posts
Showing posts with label blackout. Show all posts

Thursday, 30 September 2021

How Close is Ireland to Blackouts ?

 

                                  Chart 1 - The green line includes all potentially available capacity whether currently in use or not. Some adjustments have been made to the red line to take account of the temporary loss of two gas and one oil generators . 


The above graph shows how Ireland's electricity supply position has evolved since the height of the building boom in 2006. The green line shows the total generation capacity that consumers must pay for including wind energy. As you can see the gap between the green line and peak demand in blue has increased exponentially in tandem with the building of new wind farms in yellow and new power stations in red. This gap is a large part of the reason why electricity bills have soared in recent years as the capital element of all of this capacity must be financed through bills regardless of how much energy they produce. So with all of this excess capacity, how is it that we are facing the prospect of blackouts? 

The red line is dispatchable plant, that is, plant that can be switched on at a moment's notice as required. The main ones in Ireland are gas, coal and oil power stations. The interconnector to England (EWIC) is also included in this however it's debatable how dispatchable this is in light of recent events (more on this later). Peat is also dispatchable but two of those power stations were closed down in 2020 leaving only one remaining peat station in Edenderry which also runs on biomass. It is due to be closed down in 2023. It has now finally being accepted by almost everyone (apart from the Green Party Energy Minister ?) that wind is not dispatchable and during long periods of low wind as we have had this year it is really the red line that we are relying on to keep the lights on.

The red line takes a noticeable dip after 2020. This is to take account of the loss of three power stations during 2021 - Huntstown 400MW, Whitegate 444MW and Tarbert 243MW. This has returned us to 2007 levels of dispatchable plant. This shouldn't present a serious problem, we managed okay back then. However, there are two main differences between now and back in the Tiger days :

1) Peak demand has increased by about 10%. The peak of 5,357MW was reached in December 2020. It is likely that this will increase further this winter which means the gap between the red and the blue line in Chart 1 will narrow even further. 

2) The rate of forced outages has increased dramatically in recent years. According to Eirgrid, the forced outage rate went from a low of about 3% in 2016 to a high of about 16% in 2021. The forced outage rate is the rate at which power stations are breaking down. Power stations are becoming less reliable and not just old ones. One reason for this is that they are switching on and off too much to balance the wind (more here) . 

The situation then is precarious enough but what happens if the UK does not have spare energy to give to us over the interconnector ? This has become a greater risk as energy shortages have recently become a major political issue in the UK. Chart 2 shows what happens when the EWIC is no longer available :



Chart 2


There is now a very small gap between the red and blue lines. 353MW to be exact. Which is about the size of a single power station. So another power station outage would leave us on the precipice and if the winter is a cold one demand will surely rise pushing us over the edge into blackout territory. 

To sum up here, it would take six events occurring at the same time to leave us in a very dangerous position - three of those are the three currently unavailable power stations not being repaired in time for winter, the fourth is the interconnector becoming useless, the fifth is either another power station breaking down or demand rising higher than last year. The trend for the fourth and fifth events is going the wrong way in all cases. The likelihood however of all 3 power stations not being repaired in time for winter is fairly slim although I have a feeling Whitegate may not be repaired by mid November as scheduled.

The sixth event is perhaps the biggest variable of all, the yellow line in the charts - wind energy. If there is plenty of it then in theory the majority of these events occurring simultaneously would not pose such a major problem. But if we have another lull as we have had this summer then that is a different story.

I say, in theory, because it is slightly more complicated than that. Certain power stations are required to be operating at all times to maintain the stability of the grid. Currently that includes Moneypoint coal power station. Moneypoint happens to be the oldest power station on the grid so there is a risk to the entire grid if it alone suffers an outage. No amount of wind energy can replace the inertia that Moneypoint provides to the system. 

In any event, the demand of large energy users will most likely be cut before we get near the precarious position of all or most of these events occurring together. 

Demand management they are calling it. Which is another form of blackout, just with a nicer name . 


Saturday, 18 September 2021

Record Prices hit the Irish Electricity Market

 On Thursday the 9th September, prices in the All Ireland Electricity Market hit record highs of €4,680 per MWh, well over 20 times the normal price :


The scale here is from €0 to €5,000 MWh


What a normal day looks like, prices rise to about €150 MWh


These prices may have had something to do with the UK switching on coal plant that same week, the cost of which can be very high. Margins are set to get even tighter in the UK as this week one of the interconnectors to France went on fire causing wholesale prices to rise even higher there. Low outputs of wind energy have plagued both Ireland and the UK for many months now. In essence, high prices in the electricity market go hand in hand with low amounts of reliable generation.

There have been three Amber Alerts and seven Notifications of Tight Generation Margins issued this month in the Single Electricity Market (SEM). An Amber Alert means there was expected to be enough energy to meet demand, but possibly not enough in reserve should something go wrong. They can also be issued if there are significant frequency / voltage deviations which can happen when there aren't enough large power stations on the grid. The notification of Tight Generation Margins seems to be a prelude to an Amber Alert. 

System Alerts can go from Alert (Amber) to Emergency (Red) to Blackout (Blue) and finally to a Restoration state. Up to the end of August of this year there have been six system alerts on the grid. In the previous decade, they averaged just one per year.








Tuesday, 15 December 2020

Amber Alert With More Generation ?

 Eirgrid warned this week of an Amber Alert due to high peak demand, a loss of a number of generators and low wind generation :

“There were a number of reasons that gave rise to Wednesday’s alert. Firstly, two of the three units at Moneypoint, the country’s largest power station, suffered technical failures and were not available. This resulted in the loss of 570 megawatts of electricity.

“Generation at Whitegate power station in Cork totalling 450 megawatts was also unavailable due to technical issues. A 243 megawatt generator at Tarbert power station was called up but could not respond due to technical problems. 

“The electricity market was set up for Ireland to export renewable energy via the two interconnectors (EWIC in the South and Moyle in the North) linking Ireland and GB.

“Following the issuing of the amber alert we were able to reverse the flows on the Moyle Interconnector and on EWIC shortly after that. There was also a drop in wind generation greater than was forecast prior to the alert being issued.

“There was no loss of electricity during the alert which ended by 6.20pm on [Wednesday],” the spokesman explained.


 Apparently the last time we hit such a demand was back in 2010 but there was no mention of an alert back then. In 2010 there was 1,405MW of wind installed on the grid. In 2019 this reached 4,235MW (+2.8 GW). The 500MW EWIC interconnector was commissioned in 2012. 

So the question has to be asked, how is it that with 3.3GW of additional generation equipment, we are now struggling to meet demand? 


 

Tuesday, 3 April 2018

Storms Linked to Power Station Trips

Eirgrid published this list of power station trips from the past few months:




I couldnt help but notice that most of these dates coincided with storms or very windy conditions:

5th october - Cyclone Xavier
12th october - Hurricane Ophelia
16th october - Hurricane Ophelia
21st october - Storm Brian
27th November - gale force winds
24th December - record wind penetration on the grid
3rd January - Storm Eleanor
17th January - Storm Fionn

It appears that as very high amounts of wind generation is allowed into the grid, the frequency can drop to a dangerously low level.


One of our key tasks is to maintain balance between electricity supply and electricity demand. Electrical frequency is the measure of balance between supply and demand. When supply and demand are balanced, the electrical frequency is at 50 Hz. We must maintain this balance on the system all day, every day. The normal operational frequency range is 49.8 Hz to 50.2 Hz [Eirgrid].

You can see from the above diagram that the frequency has dropped below 49.8Hz on a few occasions over this period.  As a result, the power station tripped and went offline. This then results in the frequency falling even further. At this stage, cutting demand is one of the few options open to the grid operator. This may explain some of the blackouts on these days.

Monday, 2 November 2015

South Australia - What A Future With Wind Energy Looks Like

Interconnectors and Wind Energy go hand in hand. Like South Australia, Ireland has had bad experiences with interconnectors. The Moyle Interconnector linking Scotland and Northern Ireland went out of action in 2011 and since then only half of its capacity is working. Wind energy, as we all know, is intermittent and cant be relied on to produce power when needed. Hence, why it is given a very low capacity credit. So if you combine the two you are asking for trouble. S.Australia experienced a blackout yesterday - here is what a "Green" future looks like :



“We’ve always relied to some degree on the Victorian interconnector — that’s why it’s there, it’s been there for 25 years.
“Many times other supply will kick in and there’s always stuff on standby, but in this case it may well have been the size of the load.”
When the Victorian system shut down, 160 megawatts of energy was lost and wind power did not supply energy because it often does not start until 3am.
Mr Roberts said when outages were planned, people on life support were notified.
But last night’s blackout “caught everyone by surprise”, despite the fact Victoria had issued a low level risk notice for a power outage for the past seven weeks.
Mr Roberts said a review would be conducted into the widespread outage.

Tuesday, 2 December 2014

SEAI's Quantifying Savings from Renewables Report and the Impact of Wind on Reserve Requirements


Earlier this year, SEAI issued a report, which concluded that there was a saving of € 177 million in fossil fuel due to wind generation in 2012, titled "Quantifying Ireland's Fuel and CO2 Savings from Renewables". The report has a number of flaws. Here is a sample of some of those flaws :


  1.  For the "No Wind" model, it assumes that the wind capacity would be replaced by 180MW of OCGT. OCGT is the most inefficient form of gas generation and would therefore result in larger savings than a CCGT plant in their "2012 Base Model" with wind. They could have replaced this capacity with biomass for example, like what is happening in Edenderry Power Plant which would have resulted in much less emissions, thereby decreasing their final savings figure. It also could have been replaced by the replacement of HFO plant with CCGT plant, as in Great Island, which in that case, resulted in a net increase in capacity of about 200MW.
  2. The report states that "The total quantity of ramping in coal generation is higher with renewable electricity on the system. In contrast, gas CCGTs vary their output by a lesser amount with renewable electricity on the system." This is utter nonsense. You can have a look at the ramping profiles of CCGT plant here [Aghada] and here [Dublin Bay]. With more wind in the system, the ramping of gas plants is multiples of what it is in a system with little or no wind (as the only variable is demand).
  3. Number 2 also disproves the claim made that "Wind generation variability in 2012 was less than electricity demand variability". If this were the case, then the graphs linked above, would show the opposite, i.e. more ramping in the no wind or little wind periods or at least similar ramping but the difference is huge. Aghada CCGT's load profile for example has a flat surface in 2009 when there was only small amounts of wind compared to the jagged surface of 2013 when there was much more wind.
  4. The assumptions made on the inefficiencies of generators at different loads - Gas is responsible for 78% of the quantity of savings in the report. Most of that is made up of CCGT. To allow 200MW of wind in the system, a typical 400MW CCGT gas plant must drop to 200MW. This results in increased CO2 emissions of about 0.05- 0.07 tonnes per MWh, an increase of 20%. To allow more wind in, the efficiency drops further and CO2 emissions increase at a faster rate as explained here. So to allow 4,094GWh of wind in to create the assumed savings in the report, CO2 emissions would rise even more than 0.07 tonnes at times.  but they assume that "With the actual level of renewables on the system in 2012 (the Base Model case), the CO2 emissions intensity of fossil-fuel generators is 5% higher than in the No Wind Scenario." In reality, this would be higher, thereby eating into their savings figure due to wind.  
  5. Likewise there is an efficiency drop of 8% from 58% to 50% in the above scenario in Number 4. To allow more wind in, the efficiency drops further and at a faster rate. So to allow 4,094GWh of wind in to create the assumed savings in the report, the efficiency would most likely fall below 50% at times and even to 40% (a drop in efficiency of 18%). So the average efficiency of the CCGT plant is somewhere between 48%-52% (48% being a conservative base figure). This is a drop in efficiency of between 8% and 10%.  We are not told the efficiency figures they use. If higher efficiencies are assumed, then their fossil fuel saving figure is inaccurate.
  6. Perhaps the biggest flaw is their assumptions on reserve - and more importantly, replacement reserves, which increases when large amounts of wind are allowed into the system. A practical example is shown in a previous blog post here. You can see that CCGT plant had to be kept ticking over (just like a car left on and parked outside your house) to step in instantly as the wind dropped off. As this plant stepped in, replacement reserve needs to be made available in the event of a forced outage of another plant or indeed, a further drop in wind. Therefore, there tends to be a peak demand for reserves and replacement reserves at high levels of wind penetration. Let's look into this important matter in more detail:

The Impact of Wind on Reserve Requirements


 In a 2007 report, prepared for Eirgrid, titled "Wind Variability Management Studies (P.Meibom et al)" , Danish scientists and University researchers concluded that:
 "Generally, the demand for replacement reserves increases with
increasing wind power capacity installed.
The occurrence of high demands for replacement reserves is
mainly driven by a high number of simultaneous forced outages that happens
simultaneously to relatively high wind power or load forecast errors. The value of these peaks tends to increase with increasing wind power capacity installed."
In another study by R. Doherty and M. O’Malley of UCD Dept of Electronic and Electrical Engineering, titled “A new approach to quantify reserve demand in systems with significant installed wind capacity,” it was stated that :

The methodology is applied to a model of the all Ireland electricity system, and results show that as wind power capacity increases, the system must increase the amount of reserve carried or face a measurable decrease in reliability [i.e. increase the risks of a blackout - bloggers note].
[Note that in these reports, they assume that increased wind capacity (i.e. building more wind farms) will result in higher wind penetration in the system (i.e. higher levels of wind relative to demand)]

SEAI took no account in their study of the increased demand for reserves during periods of high wind penetration i.e. more plant burning fuel behind the wind. Instead, they took a fixed amount of reserves during the year based on the minimum amount of reserve permitted by the regulations :

Primary and secondary operating reserves are calculated dynamically in the model for each period based on 75% of the largest unit running at that time in RoI and the largest unit running at that time in NI. Tertiary reserve requirements are included as fixed quantities based on the largest single electricity in-feed. These were 425 MW in NI and 480 MW in RoI for the first 9 months of 2012 and 500 MW for the last 3 months of 2012 [SEAI].

Lets have a look at the Regulations :



That's right, this is the Minimum amount of reserve that must be maintained. It is then at the discretion of the TSO (Eirgrid) to increase this depending on circumstances.


Reserve requirements are not influenced by wind generation or other renewable electricity generators at current levels of installed capacity. [SEAI]

However, it was still possible that there could have been high levels of wind penetration in 2012 (which would have resulted in increased demand for reserves).
The All-Island grid study showed that additional reserve requirement in hypothetical 2020 scenarios is related to the amount of wind installed but that the largest contributing factor remains the loss of the largest conventional unit [SEAI].
The study SEAI are referring to is the same report by Danish scientists mentioned above. But what the study actually says in relation to this is :

There should be enough spinning reserves to cover an outage of the largest unit in combination with a fast decrease of the current wind power production. However, the capacity of the largest online unit changes dynamically. (Doherty and O’Malley 2005) further demonstrate the dependency of the demand for TR1 [Reserve Type 1] from the installed wind power capacity. 
SEAI also argue that the system in Ireland is flexible enough to accommodate fluctuations in wind anyway without the need for additional reserve. But as you can see in the example previously mentioned (see here), you can see where two CCGT plants, namely Huntstown and Great Island, stepped in from reserve to cover the loss in wind power on the 3rd November. None of the online plants were flexible enough or had enough spare capacity to provide this cover.

We can look at the impact of wind on reserve with a very simple example. Say, that we end up with a system, where 100% of the wind can be allowed in to meet 100% of demand and this occurs for a whole day. By the following day, 20% of the forecasted wind drops off, and then later in the day 50% of the remaining forecasted wind drops off. By the 3rd day, wind is only providing 5% of demand. Now let's pretend that we do what SEAI say we should do and maintain 480MW-500MW of reserve. Remember, Reserve requirements are not influenced by wind generation. As the 20% wind drops off, we will be able to call on the reserve by ramping up the reserve generators to full output to fill the gap. We must now put replacement reserve in place. Again, this is not affected by the wind so 500MW will do fine. But now we come to later in the day where circa 1,500MW wind has dropped off. We use some of our fast acting (but small capacity) units to try to fill the gap along with the other slower replacement reserve. But there is simply not enough of the slower acting, larger capacity reserve ready to step in. Time has run out and we are now facing Blackouts. So it is clear from this example, that you have to increase the minimum reserves to cover nearly every MW of wind in the system, thereby negating most, if not all, of the fossil fuel or CO2 savings (actually potentially increasing them because the back-up plant have to run on low loads). The wind, itself, in effect, becomes the largest in-feed unit. You can get away with lower reserves at lower levels of wind, but you simply can't take this risk at higher levels.

So, there is no debate on this - increasing wind penetration above a certain level, leads to an increase in reserves. I would put the line at 1,000MW in the Irish system, as now we have the equivalent of two large thermal plant that can drop out at any time and in any sequence and is much more likely to drop out than if they were in fact, two thermal plant. The exact amount can be debated but I will now come to a problem with the report, that presents a fundamental issue for those who are now using it to inform energy policy and public debate. It is there, written down exactly as quoted here, on Page 12, and can't be debated or argued over, or fudged, or ignored, or interpreted in some other fashion.

The main problem with this report is that it gets trotted out by SEAI and policymakers as the basis for installing more wind farms. But, like with previous SEAI reports, there is a huge disclaimer in it, that most people who have read it may well have missed. That is why I put it in bold above. But it deserves repeating and repeating again :


Reserve requirements are not influenced by wind generation or other renewable electricity generators at current levels of installed capacity


So I ask the question, why is this report, long outdated and now redundant, since it is based on 2012 levels of wind in the system, trotted out and used as justification for more wind farms when what it really is saying, just like all the other reports mentioned above, (albeit begrudgingly in this case) is that the integration of more wind in the system will require more fossil fuel reserves ?


Tuesday, 11 November 2014

The Limit on Wind and Interconnection in the System


Graph for 18th October, 2014:





At present, the maximum amount of power from wind generation and interconnection that can be accommodated into the grid at any one time is 50%. This was confirmed by Eirgrid in their System Operational Constraints update back in March this year. In March, when the capacity factor of wind was 33%, this limit had been reached, with the excess wind power "constrained" off.  In December 2013, when wind had a capacity factor of over 50%, this limit was met on twelve different days.   Given this situation, it is curious that the current Irish energy policy revolves around more interconnection and more wind.

The problem is that wind and imported power provide "non synchronous" power which is incapable of providing the type of stable power produced from conventional sources. Exceeding this limit of 50% will alter the frequency of electricity sent to houses and factories damaging equipment and tripping the switches on the grid causing a blackout. There are efforts underway to change what is known as the "rate of change of frequency" (RoCoF) to try to accommodate more non synchronous generation but it is still not known if conventional plant can withstand these fluctuations or operate at the ranges required. Conventional generation operators claim that it could take several years before these questions can be answered. They are also worried about the costs involved with no additional benefits for them. Presumably, the consumer will eventually pick up the cost for this potentially disastrous experiment.

Eirgrid are now using a new computer tool since May called WSAT (Wind Security Assessment Tool) which monitors the amount of non-synchronous generation in the system at any one time. An example of the limit being reached recently can be seen on the 18th October (see graph above). At 14.45 during the day, wind generation was hovering around the 1,500MW mark. It had begun to rise further as demand had begun a downward trajectory. At this point demand was 2,985MW, Wind 1,561MW and the East West interconnector was exporting 54MW to the UK. The net non-synchronous power was 1,507MW, 50% of demand. Eirgrid then "shut off" 200MW of wind to bring back stability to the system. The new Great Island CCGT gas plant (presumably on testing mode) saved the day ramping up quickly to fill the gap. North Wall and Aghada OCGT also provided some additional peaking power from a more inefficient gas source.



So the next time you hear someone talking about powering the electricity grid with 100% wind or a politician talking about the need for more interconnection, you will know they are talking beyond their expertise.